Refrigeration and air conditioning notes: vapour compression cycle summary

Refrigeration and Air Conditioning Notes: Cycles, Refrigerants and Psychrometrics

Refrigeration removes heat from a cold space and rejects it to a warmer one, and air conditioning controls the temperature, humidity and cleanliness of air. These notes cover the main cycles, refrigerants and psychrometrics with formulas and solved examples. Revise thermodynamics first if the cycle diagrams feel new. Keep these refrigeration and air conditioning notes open while you revise for exams and viva.

Refrigeration and air conditioning notes: vapour compression cycle summary

1. Basic terms

  • Refrigerating effect: heat absorbed by the refrigerant in the evaporator per kg.
  • Ton of refrigeration (TR): 1 TR = 3.517 kW (about 211 kJ/min), the cooling needed to freeze one tonne of water at 0 °C in 24 hours.
  • Coefficient of performance (COP): COP = refrigerating effect / work input.

For a reversed Carnot refrigerator, COP = TL / (TH − TL), with temperatures in kelvin. No real refrigerator can exceed this value.

2. Vapour compression refrigeration cycle

This is the most used system in refrigerators, air conditioners and cold storage. It has four processes:

  1. Compression (1–2): the compressor raises the pressure and temperature of the vapour.
  2. Condensation (2–3): the vapour rejects heat in the condenser and becomes liquid.
  3. Expansion (3–4): the expansion valve or capillary tube drops the pressure at constant enthalpy (h3 = h4).
  4. Evaporation (4–1): the cold liquid absorbs heat in the evaporator and becomes vapour.

With enthalpies read from the p–h chart or tables:

Refrigerating effect = h1 − h4   |   Compressor work = h2 − h1   |   COP = (h1 − h4) / (h2 − h1)

Superheating the vapour before the compressor and sub-cooling the liquid after the condenser both increase the refrigerating effect. Lower evaporator temperature or higher condenser temperature reduces the COP.

3. Refrigerants

A good refrigerant has a high latent heat, suitable pressures, low freezing point, chemical stability, and is safe and cheap. Environmental impact is measured by ODP (ozone depletion potential) and GWP (global warming potential). Older CFCs (R-12) and HCFCs (R-22) are phased out; R-134a is widely used but has a high GWP. Modern choices are R-600a (isobutane) in domestic refrigerators, R-290 (propane), R-32 and R-1234yf in cars. Ammonia (R-717) is used in large cold stores because it is efficient, but it is toxic.

4. Vapour absorption system

Instead of a compressor, an absorption system uses heat. The refrigerant vapour is absorbed in a liquid in the absorber, the solution is pumped to the generator where heat drives the refrigerant out again, and the rest of the cycle is like the vapour compression system. Common pairs are ammonia–water and lithium bromide–water. It suits places with waste heat or solar heat and gives quiet operation, but its COP is lower than a vapour compression system.

5. Other systems

Air refrigeration (reversed Brayton cycle) is used in aircraft cabins. Steam jet and thermoelectric refrigeration are used in special cases. Multi-stage compression with inter-cooling is used when the pressure ratio is high.

6. Psychrometrics

Psychrometrics deals with moist air. Key properties are:

  • Dry bulb temperature (DBT): normal air temperature measured by a dry thermometer.
  • Wet bulb temperature (WBT): measured with a wet wick; it is lower than DBT unless the air is saturated.
  • Dew point temperature (DPT): temperature at which moisture starts to condense when air is cooled at constant pressure.
  • Relative humidity: φ = pv / pg (vapour pressure over saturation pressure at the same DBT).
  • Specific humidity: ω = 0.622 × pv / (p − pv) kg of vapour per kg of dry air.

Basic psychrometric processes are sensible heating and cooling (ω constant), humidification and dehumidification, cooling with dehumidification (air-conditioning coil), adiabatic saturation and mixing of two air streams.

7. Air conditioning

Comfort air conditioning keeps the room at about 22–26 °C and 40–60% relative humidity. The cooling load includes heat entering through walls and roof, solar heat through glass, people, lights, equipment and fresh air. Loads are split into sensible heat (SH) and latent heat (LH), and the sensible heat factor SHF = SH / (SH + LH). Common systems are window and split units, packaged units, VRF systems and central chilled-water plants. Cooling towers and evaporative coolers use evaporation of water for cooling.

Solved examples from these refrigeration and air conditioning notes

Example 1: Carnot COP

A refrigerator works between −10 °C and 30 °C. Find the maximum possible COP.

TL = 263 K, TH = 303 K. COP = 263 / (303 − 263) = 6.58.

Example 2: Vapour compression cycle

In a simple cycle h1 = 395 kJ/kg, h2 = 430 kJ/kg and h3 = h4 = 240 kJ/kg. Find the COP and the refrigerant flow rate for 5 TR.

Refrigerating effect = 395 − 240 = 155 kJ/kg. Work = 430 − 395 = 35 kJ/kg. COP = 155 / 35 = 4.43. Cooling = 5 × 3.517 = 17.585 kW, so mass flow = 17.585 / 155 = 0.113 kg/s.

Example 3: Specific humidity

Moist air at 101.325 kPa has a vapour partial pressure of 1.8 kPa. Find the specific humidity.

ω = 0.622 × 1.8 / (101.325 − 1.8) = 1.1196 / 99.525 = 0.01125 kg/kg of dry air.

Summary of the refrigeration and air conditioning notes

In short, the refrigeration and air conditioning notes on this page give you the main ideas, formulas and solved examples in one place. Read the refrigeration and air conditioning notes once for understanding, then revise only the formulas and the quick points. If you find a topic difficult, solve its example again and compare each step with the solution given above.

Refrigeration and air conditioning notes: quick revision points

Use these refrigeration and air conditioning notes as a short checklist before your exam, viva or project review. Read the points once, then open the matching section above for the formula or example.

  • Revise the COP, ton of refrigeration and Carnot COP formulas.
  • Remember the four processes of the vapour compression cycle and the enthalpy equations.
  • Know ODP and GWP and give examples of modern refrigerants.
  • Be clear on how vapour absorption differs from vapour compression.
  • Learn DBT, WBT, DPT, relative humidity, specific humidity and sensible heat factor.

Good refrigeration and air conditioning notes are short, clear and full of worked examples. Come back to this page whenever you need to revise, and use the related pages below to practise.

For a general overview of the topic, you can also read the vapour-compression refrigeration article on Wikipedia.

Frequently asked questions about refrigeration and air conditioning notes

Why is an expansion valve needed?

It lowers the pressure of the liquid refrigerant so that it can evaporate at a low temperature in the evaporator.

What does 1.5 ton AC mean?

The air conditioner can remove about 1.5 × 3.517 = 5.3 kW of heat from the room.

Why is R-22 being phased out?

It has ozone-depleting potential and a high global warming effect, so newer refrigerants with lower impact are replacing it.

Are these refrigeration and air conditioning notes enough for my exam?

These refrigeration and air conditioning notes cover the core topics with formulas and solved examples, so they are a strong base for semester exams and viva. For full marks, also practise problems from your university textbook and previous question papers.

Related: Thermodynamics · Heat Transfer · Fluid Mechanics · Mechanical engineering MCQs

Viva preparation: Refrigeration and Air Conditioning viva questions with answers.