As the world gets hotter, air conditioners are running longer and using more electricity than ever. At the same time, every split AC drips away litres of cold condensate water that forms on the indoor coil. This water is usually wasted, even though it is cooler than the outside air. This project uses that condensate to improve the AC itself. The idea is to pass the hot refrigerant line through the cold condensate, so the refrigerant is subcooled below its condensing temperature before it reaches the expansion device. Subcooling increases the cooling effect per kilogram of refrigerant, which raises the coefficient of performance and reduces power consumption.

How Condensate Subcooling Works
In a normal vapour compression cycle, the refrigerant leaves the condenser as a liquid close to its saturation temperature. If it can be cooled a few degrees further, more of it stays liquid after the expansion valve, so it can absorb more heat in the evaporator. In this design:
- Condensate water from the indoor unit is collected in an insulated tank.
- A copper coil carrying the hot refrigerant passes through the tank.
- Heat moves from the refrigerant into the cool water, subcooling the refrigerant.
The experimental reference unit uses R22 refrigerant with a compressor capacity of about 0.75 kW.


Refrigerants Compared
The project also looks at the eco-friendly refrigerant R290 (propane) as an alternative to R22:
| Property | R22 | R290 |
|---|---|---|
| Chemical name | Chlorodifluoromethane | Propane |
| Molecular mass | 86.48 | 44.1 |
| Boiling point at 101.325 kPa (°C) | −40.76 | −42.09 |
| Critical temperature (°C) | 96 | 96.7 |
| Critical pressure (kPa) | 4974 | 4248 |
| Ozone depletion potential | 0.055 | 0 |
| Global warming potential | 1810 | 3 |
| Safety class | A1 | A3 |
About the Project
The AC outdoor unit, condensate tank and copper coil are modelled in SolidWorks. The tank and coil are then analysed in ANSYS Fluent to study heat transfer between the refrigerant and the condensate water. Four design cases are studied with the same boundary conditions: tank water inlet at 20 °C and 0.002 m/s, and coil inlet at 45 °C and 0.001 m/s. The materials are copper for the coil (thermal conductivity 387.1 W/m-K), water (0.6 W/m-K) and an insulating tank wall.


Software Used
- SolidWorks: AC unit, tank and coil modelling
- ANSYS Fluent: conjugate heat transfer CFD

The temperature results for all four cases, the subcooling achieved and the final design recommendation are explained in the project report.
Real-World Applications
- Split and window ACs: low-cost efficiency upgrade.
- Commercial HVAC: reusing condensate from large air handling units.
- Refrigeration systems: liquid line subcoolers.
- Green buildings: water and energy recovery.
Key Concepts Covered
- Vapour compression cycle and coefficient of performance.
- Subcooling and its effect on refrigerating effect.
- Refrigerants: ODP, GWP and safety.
- Conjugate heat transfer CFD between a coil and water.
Project Workflow
- Study AC cycles and subcooling methods.
- Design the condensate tank and copper coil.
- Model the AC unit and heat exchanger in SolidWorks.
- Run CFD in ANSYS Fluent for four cases.
- Compare the temperature drop in the report.
Why This Project Matters
Small efficiency gains in air conditioners add up to huge energy savings across millions of units. This project turns a waste stream into a performance booster, which makes it a strong sustainability-focused final-year project.
Related Projects
Explore more design and analysis projects on similar topics:
- Li-ion Battery Pack Thermal Management with Paraffin PCM and Copper Tube Water Cooling (SolidWorks and ANSYS)
- CFD, Static and Thermal Analysis of a Steam Boiler Used in Power Plants with Steel, Brass and Steel 316L (SolidWorks and ANSYS)
- Radiant Heat Exchanger Heater – Static and Thermal Analysis with Steel, SAE 1020 and Steel 416
- Heat Exchanger with Circular and Tapered Inserts – CFD Analysis with Nanofluids
What You Get
- Design files: SolidWorks models of the AC outdoor unit, condensate tank and copper coil heat exchanger
- Analysis files: ANSYS Fluent CFD files for the condensate tank and coil under four cases
- Project document: complete report with methodology, results and conclusion
- Class explanation: a session that explains what was done in the project, step by step, so you can understand and present it confidently
Who Is This Project For?
This project suits B.Tech and B.E. final year students, diploma students looking for a strong design and analysis project, and M.Tech students who need a base model they can extend for their thesis. It is also useful for anyone who wants to learn SolidWorks modelling and ANSYS Fluent heat transfer analysis on a real engineering problem instead of a textbook example.
Frequently Asked Questions
What is subcooling in an air conditioner?
It is cooling the liquid refrigerant below its condensing temperature, which increases the cooling effect and improves efficiency.
How does this project use condensate water?
The cold water dripping from the indoor unit is collected in a tank, and the refrigerant line passes through it in a copper coil to be subcooled.
What boundary conditions are used in the CFD analysis?
Tank water inlet at 20 °C and 0.002 m/s, and coil inlet at 45 °C and 0.001 m/s, for four design cases.
Which software is used?
SolidWorks for modelling and ANSYS Fluent for heat transfer analysis.
Get the AC Subcooling with Condensate Water Project
Want this project for your final year, mini project or M.Tech work? Message us with your university, branch and deadline, and we will share the exact scope, files and report format.
Enquire about this project on WhatsApp or use the enquiry form on our home page. Browse more mechanical projects or 60+ mechanical engineering project ideas.
Interested in this project? Get the details, files and guidance from our team.
Enquire on WhatsApp